Blog/24 November 2022

Preparing your chiller for winter

Six steps to winterise water-cooled chillers: draining or glycol for idle units, checking glycol concentration, keeping coils clear, checking high-side pressures, running the pump and planning ahead.

Published
24 November 2022
Reading time
2 min
Author
Tehnogama tim
Preparing your chiller for winter

Chillers are refrigeration units that produce cold water for cooling spaces or production processes. Chiller condenser units can be air-cooled, water-cooled or a combination of both.

This short reminder is about water-cooled chiller condenser units.

All chillers used in air conditioning and industry that are exposed to outside temperatures below 3 °C on cold days must be properly prepared for the coming winter. The first step is to check the glycol concentration in the system.

011. Winterising chillers that do not run in winter

These units require the water to be drained from the system (cooler). It is also recommended to fill the chiller with a mixture of glycol and water. This prevents freezing and the formation of ice on the heat exchanger, pump, tank and valves.

022. Winterising chillers that run in winter

For these units, check the glycol concentration in the coolant. Glycol concentration tables will help you determine the right concentration for given temperatures, and a refractometer will let you check the glycol level in the system.

033. Keep condenser coils clean and free of snow and ice

Ice and snow can damage fan blades and block airflow through the condenser, reducing the chiller’s cooling capacity.

044. Check high-side pressures manually

In extremely cold ambient conditions, high-side pressures can drop. If your chiller has no low-ambient control, such as fan cycling or a flooded condenser, it may not be able to operate properly. In that case, if the temperature falls below the nominal high-pressure (HP) temperature, airflow through the condenser coil and fan should be blocked by wrapping them in plastic film or blocking the flow with cardboard. This is certainly not a “high-tech” solution, but it will serve as a temporary fix during unusually low temperatures.

055. Keep the pump running

While the chiller is running, your process most likely provides enough warm water to keep the fluid above freezing or above the glycol’s freezing point. At night or when the process is idle, however, the water temperature can drop sharply. Keeping the pump running adds the heat the pump gives off and heat from the room – and moving water freezes much later than standing water.

066. Plan ahead

The best way to prepare your chiller for winter is to plan ahead. When choosing and buying a chiller, make sure you include the cold-weather option. Do your winter maintenance by the end of September: if adjustments or corrections to the system are needed, there is enough time between then and the first very cold days.

Share

Related articles

All articles →
Oil-free air – for real!
21 May 20254 min read

Oil-free air – for real!

BOGE bluekat: how a standard oil-lubricated screw compressor reaches ISO 8573-1 Class 0 through catalytic treatment – with lower investment, simpler maintenance and no oil in the condensate.

Read article
Tehnogama online shop Rental centar Tehnogama
Tehnogama · Newsletter

Subscribe to our newsletter

New articles, maintenance tips and offers — once a month.

Service 24/7+381 22 215 23 02
HeadquartersTehnogama d.o.o. · Šimanovci