Blog/25 July 2024

Ventilation in the compressor room

How much heat a compressor releases, why the exhaust fan should be 2–3 times larger than the compressor fan, and where to place intake louvres and exhaust openings.

Published
25 July 2024
Reading time
2 min
Author
Tehnogama tim
Ventilation in the compressor room

Several factors determine how your compressor will perform in hot summer weather. The amount of air available to cool the compressor is one of the most important.

Air-cooled compressors are cooled by an internal fan that pushes or pulls air over a radiator-style cooler. Compressor specifications always state the airflow (in CFM) and the allowable static pressure (in inches of water column) – for example, 8000 CFM @ 0.25” H2O.

To maintain optimal cooling, the compressor must be installed where this airflow can actually take place. If it is connected to a ventilation duct, the duct must be sized so that the pressure drop in the ducts (inlet and outlet) stays below the maximum allowable pressure. If the ducts are too small, an auxiliary fan may need to be added.

01How much heat does a compressor release?

If the compressor stands in an open room, the room must be large enough to dissipate the heat the compressor generates. A compressor rejects roughly 2,500 BTU/h per horsepower, so a 100 HP compressor will radiate 250,000 BTU/h into the room.

If the room is not large enough to dissipate the heat, an exhaust fan (and possibly intake louvres) will need to be added. A common mistake is to size the exhaust fan the same as the compressor fan. Most compressors raise the temperature of the air passing through the cooler by 10 °C.

02Size the exhaust fan correctly

If the exhaust fan removes only the same amount of air, the temperature in the compressor room will rise by 10 °C over time. If nothing, or too little, is done about room ventilation, the ambient temperature around the compressor will eventually exceed the reference value and the compressor will shut down – which is, of course, unacceptable. If the exhaust fan is sized 2 to 3 times larger than the compressor fan, the temperature rise in the compressor room will be only 3–5 °C, which is much better for the compressor and the other equipment in the room.

03Other factors to consider

The exhaust fan should be installed high in the room, while the intake louvres should be low. This supports the natural upward flow of heat – most compressors release heat from the top. If possible, the intake and exhaust openings should also be on different walls.

There are many things to consider when installing your air compressor. Proper ventilation will prevent unnecessary shutdowns and extend the service life of your compressor.

Share

Related articles

All articles →
Oil-free air – for real!
21 May 20254 min read

Oil-free air – for real!

BOGE bluekat: how a standard oil-lubricated screw compressor reaches ISO 8573-1 Class 0 through catalytic treatment – with lower investment, simpler maintenance and no oil in the condensate.

Read article
Tehnogama online shop Rental centar Tehnogama
Tehnogama · Newsletter

Subscribe to our newsletter

New articles, maintenance tips and offers — once a month.

Service 24/7+381 22 215 23 02
HeadquartersTehnogama d.o.o. · Šimanovci